순환최소자승법을 이용한 직류도시철도 변전소의 가선전압변동 모델링
초록
The DC overhead line voltage of an electric railway substation swings depending on the accelerating and regenerative-braking energy of trains, and it deteriorates the energy quality of the electric facility in the DC railway substation and restricts the powering and braking performance of subway trains. Recently, an energy storage system or a regenerative inverter has been introduced into railway traction substations to diminish both the variance of the overhead line voltage and the peak power consumption. In this study, the variance of the overhead line voltage in a DC railway substation is modelled by RC parallel circuits in each feeder, and the RC parameters are estimated using the recursive least mean square (RLMS) scheme. The forgetting factor values for the RLMS are selected using simulated annealing optimization, and the modelling scheme of the overhead line voltage variation is evaluated through raw data measured in a downtown railway substation.
키워드
- 제목
- 순환최소자승법을 이용한 직류도시철도 변전소의 가선전압변동 모델링
- 제목 (타언어)
- Modelling Voltage Variation at DC Railway Traction Substation using Recursive Least Square Estimation
- 저자
- 배창한
- 발행일
- 2015-12
- 저널명
- 전력전자학회 논문지
- 권
- 20
- 호
- 6
- 페이지
- 534 ~ 539