상세 보기
철도용 피뢰기의 열화진전에 관한 연구
- 길경석;
- 한주섭;
- 한문섭
초록
Arresters are the best protective device on electrical power systems against transient overvoltages generated by lightning and/or switching operation. Nonetheless, arresters are deteriorated by absorption of moisture in the environments of its use, repetition in the protective operation to overvoltages, and some defects at manufacturing. It is therefore important to estimate the electrical characteristic changes of ZnO blocks. In this paper, an accelerated ageing test by a standard lightning impulse current was carried out to extract parameters needed for arrester diagnosis, and leakage current components were measured. Total energy applied to the ZnO blocks at each time is about 1,050[J] in 8/20[㎲] impulse current. From the experimental results, we proposed electrical parameters and leakage current level to diagnose arrester soundness.
키워드
- 제목
- 철도용 피뢰기의 열화진전에 관한 연구
- 제목 (타언어)
- A Study on the Deterioration Progress of Railway Arresters
- 저자
- 길경석; 한주섭; 한문섭
- 발행일
- 2004-12
- 저널명
- 한국철도학회논문집
- 권
- 7
- 호
- 4
- 페이지
- 307 ~ 311
- 언어
- ENG
- 출판사
- 한국철도학회
- 발행국가
- 대한민국
- 분량
- 5 페이지
- ISSN
- E 2288-2235
P 1738-6225