냉동 물류 창고 내 도크시스템을 통한 에너지 손실량 분석

Analysis of Amount of Energy Loss for a Dock System in the Cold Distribution Center

초록

In this study, energy loss due to ventilation load in the dock system was analyzed through simulation. Also, flow generated in the dock system of the warehouse was measured using manufactured measuring devices. Numerical simulation was conducted by simulating the most common picking tasks by examining the actual working environment. Incompressible and unsteady turbulent flows were assumed, and the turbulence model was the k-e standard model. Proper grid was selected through grid dependency test. Measurement was conducted using Honeywell and Vaisala sensors, and flow and temperature inside the warehouse were measured and compared with simulation results to validate simulation. When comparing amount of loss occurring in two hours and amount of loss occurring in 15 minutes, docking time of the former was eight times longer but energy loss was 3.8 times lower. Ventilation load occurring during the initial period after opening docking system accounted for a large proportion of total ventilation load. Also, comparing the load when the dock was closed and the load when the truck was parked, ventilation load was significantly higher than load due to heat conduction from the wall. Therefore, in improving the docking system, it is effective to reduce the gap by improving compatibility of the docking system and truck, rather than wall material.

키워드

냉장 물류 창고수치해석에너지 유출Cold distribution centerNumerical analysisEnergy Loss
제목
냉동 물류 창고 내 도크시스템을 통한 에너지 손실량 분석
제목 (타언어)
Analysis of Amount of Energy Loss for a Dock System in the Cold Distribution Center
저자
양성준김영주허준김태성
DOI
10.6110/KJACR.2017.29.8.419
발행일
2017-08
저널명
설비공학 논문집
29
8
페이지
419 ~ 428