Evaluation of Current-Carrying Capacity of Copper-Cladding Steel Messenger Wire for Electric Railway

초록

In order for the feasibility study of copper-cladding steel(CCS) messenger wire, which is a newly developed overhead line for electric railway, we compared its electrical performance with that of conventional Bz messenger wire by means of evaluating current-carrying capacity for steady-state and transient-state. The current-carrying capacity was calculated with the mathematical process based on heat balance equations in accordance with IEEE standard 538. And to clarify calculated result for transient-state, we investigated the thermal durability to withstand the fault current caused by electrical contact of conductive objects. From the results, the CCS messenger wire had 20% higher steady-state thermal rating than Bz messenger wires. In transient-state, the CCS messenger wire had excellent thermal durability than Bz messenger wire. This study revealed that the CCS messenger wire had electrical performance sufficient to substitute the Bz messenger wire

제목
Evaluation of Current-Carrying Capacity of Copper-Cladding Steel Messenger Wire for Electric Railway
저자
이창영; 권성태; 김정국; 창상훈; 한영재
발행일
2008-10-13
학회명
Powercon 2008