Behavior of protection relays in the DC traction system with starting loada
- 이원석;
- 강상희;
- 박종민;
- 정호성
초록
DC traction power system is operated ungrounded so that minimize the stray current. Because the stray current is still present, a rail potential is increased. The ground faults in the DC railway systems are usually detected by a potential relay(64P). And the fault current can be smaller than the current of load starting. So it's important to discriminate between the small fault current and the load starting current. The DC fault selective relay(50F) detects a remote short circuit fault. This paper analyzed behaviors of the potential relay(64P) and the DC fault selective relay(50F) using the load starting model in PSCAD/EMTDC.