고무차륜시스템에서의 지락보호를 위한 급전선로 절연과 부극전위와의 영향 분석

An Analysis of Influence Between the Power Feeding Line Insulation and Negative Rail Potential for the DC Ground Fault Protection in the Rubber Wheel System
Citations

SCOPUS

0

초록

We have analyzed influence of potential rise in negative bus, which caused by decrease of power feeding line insulation, upon protecting method of DC ground protection device which detecting potential rise between negative bus and ground in order to detect ground fault in the rubber wheel system. For this purpose, we proposed negative potential equation between negative bus and ground and calculated negative potential according to system condition changes by estimating power feeding line insulation changes in steel wheel system and rubber wheel system, and equalizing DC power feeding system when ground fault occurred. Also, in order to estimate negative potential of real system, we modeled the rubber wheel system, and simulated normal status, grounding fault occurrence and power feeding line insulation changes. In normal status, negative potential did not rise significantly regardless of vehicle operation. When ground fault occurred, negative potential rose up over 300V regardless of fault resistance. However, we also observed that negative potential rose when power feeding line insulation dropped down under 1MΩ. In conclusion,our result shows that in case of rubber wheel system unlike steel wheel system, relay will be prevented maloperation and insulation status observation can be ensured when ground over voltage relay will be set 200V ~ 300V.

키워드

DC ground fault protection; Negative rail potential; Power feeding line insulation; Rubber wheel system
제목
고무차륜시스템에서의 지락보호를 위한 급전선로 절연과 부극전위와의 영향 분석
제목 (타언어)
An Analysis of Influence Between the Power Feeding Line Insulation and Negative Rail Potential for the DC Ground Fault Protection in the Rubber Wheel System
저자
정호성; 신승권; 김형철; 박영; 조상훈
DOI
10.5370/KIEE.2013.62.4.577
발행일
2013-04
저널명
전기학회논문지
권
62
호
4
페이지
577 ~ 583