도시철도 직류 비접지 급전계통에서의 선택 지락보호시스템의 성능평가

An Evaluation of Selective Grounding Fault Protective Relaying Technique Performance on the Ungrounded DC Traction Power Supply System
Citations

SCOPUS

2

초록

This paper presents to verify the selective grounding fault protective relaying technique for the ungrounded DC traction power supply system. This system selectively blocks fault section when grounding fault occurred. In order to perform this verification, field test facilities have been installed on Oesam substation and Worldcup-Stadium substation,and field test process has been suggested. Also, selective grounding fault protective relaying components and rail voltage reduction device have been tested with the various trial examinations. In order to compare and evaluate performance of the selective grounding fault protective relaying function, field test system was modeled and the system fault simulation results were compared and evaluated with the field test result. Performance of selective grounding fault protective relaying function was evaluated with the above-mentioned process, and the fact that the system recognizes fault section irrespective of insulation between rail and ground and fault resistance from grounding fault.

키워드

Ungrounded dc traction; Selective grounding fault protective relay; Rail potential limit device; Field test; Dc traction system model
제목
도시철도 직류 비접지 급전계통에서의 선택 지락보호시스템의 성능평가
제목 (타언어)
An Evaluation of Selective Grounding Fault Protective Relaying Technique Performance on the Ungrounded DC Traction Power Supply System
저자
정호성; 김주욱; 신승권; 김형철; 안태풍; 윤준석
DOI
10.5370/KIEE.2012.61.12.1964
발행일
2012-12
저널명
전기학회논문지
권
61
호
12
페이지
1964 ~ 1969