The present study investigated the effect of fire suppression using a mid-low pressure water mist in a carriage fire. The fire extinguishing time and temperature distributions below ceiling in the enclosed compartment of 2.9m×2.8m×5.0m were measured by stopwatch and k-type thermocouples for various fire positions. The numerical simulations were extensively performed using Fire Dynamics Simulator(FDS, Ver. 4.0) code and the predictions were compared with experimental data. The prediction results showed good agreement with the measured maximum temperature in the all cases. Whereas the predicted temperature was about 40℃ higher than the measured one after operating of water mist. The predicted fire extinguishing times were compared with those of measured data. Fires are extinguished within 200 seconds at the experiment in Case 2 and Case 3. But in Case 1 fire was not extinguished in the numerical simulation. The reason of the discrepancy between predicted and measured data was that a simple suppression algorithm has been implemented in FDS. Also, various databases of fire properties for combustible materials and more elaborate model considering the water mist were required for better predictions of the cooling and suffocation effect.
키워드
- 제목
- 중저압 물분무를 이용한 객차내 화재진압에 관한 실험 및 수치해석적 연구
- 제목 (타언어)
- An Experimental and Numerical Study on Fire Suppression Using a Mid-low Pressure Water Mist in a Carriage Fire
- 저자
- 노재성; 양승신; 유홍선; 김동현; 정우성; 장용준
- 발행일
- 2006-06
- 저널명
- 한국철도학회논문집
- 권
- 9
- 호
- 3
- 페이지
- 291 ~ 297
- 언어
- KOR
- 출판사
- 한국철도학회
- 발행국가
- 대한민국
- 분량
- 7 페이지
- ISSN
- E 2288-2235
P 1738-6225