전차선로 해빙시스템을 위한 발열시험을 통한 전차선 온도상승 특성평가

Evaluation of temperature rising characteristics for catenary deicing system through heating test

초록

This paper analyzes the temperature rising characteristics of the deicing catenary system in winter. For the composition of the deicing system, the deicing system is constructed according to the combination of various trolley wires and messenger wires applied at Korea. To compare of temperature rising characteristics, the current distribution ratio between trolley wire and messenger wire are measured and the wire temperature is measured according to the deicing current using a catenary heating test device. In case of current distribution ratio test, the current distribution ratio is measured in 82.1%: 18.9% similar to the theoretical ratio in DC supplying. As a result of temperature rising test, the temperature of Cu 150 ㎟ is increased by 1.26 °C/m at a wind speed of 0.5 m/s and 0.92 °C/m at 2.0 m/s when supplying DC 350 A, And in case of Bz 65 ㎟, when DC 95 A is supplied, the temperature rose at 0.74° C/m at 0.5 m/s, and 0.56 °C/m at 2.0 m/s. In the comparison between the theoretical equation and test result, the difference is at most 0.7 ℃. Therefore, it is confirmed that it would be appropriate to use the theoretical equation in the design of the deicing system.

키워드

Heating test; Overhead catenary system; Temperature rising characteristics; Catenary deicing system; Deicing current
제목
전차선로 해빙시스템을 위한 발열시험을 통한 전차선 온도상승 특성평가
제목 (타언어)
Evaluation of temperature rising characteristics for catenary deicing system through heating test
저자
정호성; 김주욱; 김형철
DOI
10.5370/KIEE.2021.70.9.1398
발행일
2021-09
저널명
전기학회논문지
권
70
호
9
페이지
1398 ~ 1404