상세 보기
통합형 직류철도 보호계전 방식
Integrated Protection Method for DC Railway Systems
- 강상희;
- 최창영;
- 이원석;
- 정호성
초록
DC traction power system is operated ungrounded so that minimize the stray current. Because the stray current is still present, a rail potential is increased. The ground faults in the DC railway systems are usually detected by a potential relay(64P). Moreover, if the rail potential goes high in the ordinary operating state because of the traction load, the potential relay would be maloperated. A presented protective relaying algorithm that can identify exactly the faulted region and can distinguish a ground fault from the potential rising of the rail is presented in this paper. This paper presents simulation technique that is very similar to the real operation situation using PSCAD/EMTDC.
키워드
DC railway system; Potential Relay(64P); Rail potential; Selective ground fault protection
- 제목
- 통합형 직류철도 보호계전 방식
- 제목 (타언어)
- Integrated Protection Method for DC Railway Systems
- 저자
- 강상희; 최창영; 이원석; 정호성
- 발행일
- 2011-02
- 저널명
- 전기학회논문지
- 권
- 60
- 호
- 2
- 페이지
- 285 ~ 292
- 언어
- KOR
- 출판사
- 대한전기학회
- 발행국가
- 대한민국
- 분량
- 8 페이지
- ISSN
- E 2287-4364
P 1975-8359