통합형 직류철도 보호계전 방식

Integrated Protection Method for DC Railway Systems
  • 강상희; 
  • 최창영; 
  • 이원석; 
  • 정호성

초록

DC traction power system is operated ungrounded so that minimize the stray current. Because the stray current is still present, a rail potential is increased. The ground faults in the DC railway systems are usually detected by a potential relay(64P). Moreover, if the rail potential goes high in the ordinary operating state because of the traction load, the potential relay would be maloperated. A presented protective relaying algorithm that can identify exactly the faulted region and can distinguish a ground fault from the potential rising of the rail is presented in this paper. This paper presents simulation technique that is very similar to the real operation situation using PSCAD/EMTDC.

키워드

DC railway system; Potential Relay(64P); Rail potential; Selective ground fault protection
제목
통합형 직류철도 보호계전 방식
제목 (타언어)
Integrated Protection Method for DC Railway Systems
저자
강상희; 최창영; 이원석; 정호성
발행일
2011-02
저널명
전기학회논문지
권
60
호
2
페이지
285 ~ 292