접지망 시뮬레이션을 통한 직류 전기철도에서의 위험전위 분석

Analysis of dangerous voltage using grounding DC electric railway system

초록

DC Electric Railroad, the Isolation Grounding and the Common Grounding are grounding methods. In country Isolation Grounding use generally, but recent communication field and partial electric field apply Common Grounding. Because use Isolation Grounding mixed with Common Grounding. Dangerous voltage in the grounding system is the ground-net safety and unsafety to divide standards that very important element. MALT of CDEGS program utility analyze simulation model-1, 2, 3 in current distribution, touch voltage, and step voltage. Simulation model-1. make use of not only Common Grounding in electric power system but also Isolation Grounding in communication equipment and etc. And simulation model-2. use Common Grounding in all equipment. Simulation model-3. use Common Grounding that gathered station three-spot. As simulation conclusion is verified stable model in simulation 2. rather than simulation 1. and simulation 3. rather than simulation 2. Common Grounding apply all station and electric power system given by the IEEE. Consequently safety support of the human body as well as electric equipment.

제목
접지망 시뮬레이션을 통한 직류 전기철도에서의 위험전위 분석
제목 (타언어)
Analysis of dangerous voltage using grounding DC electric railway system
저자
김진희; 정호성; 김형철; 조대훈; 류청희; 남승욱
발행일
2011-04-29
학회명
2011 대한전기학회 춘계학술대회