GROUND FAULT PROTECTIVE RELAYING SCHEMES FOR DC TRACTION POWER SUPPLY SYSTEM

Ground fault protective relaying schemes for DC traction power supply system

초록

In DC tracking power supply system, ground faults are currently detected by the potential relay, 64P. Though 64P relay detects ground fault, it cannot identify the faulted region which causes long traffic delays and safety problem to passengers. Two new ground fault protective relay schemes that can identify the faulted region are presented in this paper. One is bus differential protective relay and the other is ground over current protective relay. Both type of relays is similar in principle to the ordinary bus differential protective relay and the ground over current relay used in other power system. In DC traction power supply system, since it is ungrounded, ground fault current is not big enough to operate those relays. To solve the problem, a current control device, called device ’X’, is newly introduced in both system, which enables large amount of ground fault current flow upon the positive line to ground fault. Algorithms for these relays are developed and their validity are verified by EMTP simulation.

제목
GROUND FAULT PROTECTIVE RELAYING SCHEMES FOR DC TRACTION POWER SUPPLY SYSTEM
제목 (타언어)
Ground fault protective relaying schemes for DC traction power supply system
저자
정상기정락교조홍식권삼영
발행일
2005-07-11
학회명
ICEE 2005