존 모델을 이용한 종류식 배연 터널 화재시 연기 거동에 대한 수치해석적 연구

A Numerical Study on Smoke Movement in Longitudinal Ventilation Tunnel Fires Using a Zone Model

초록

Many researches have been performed to analyze the smoke movement in tunnel fires by using field model. Recently, FDS(Fire Dynamics Simulator) v.4, which is one of the field model and developed from NIST(National Institute of Standards and Technology), is widely used. In tunnel fires, FDS can show detail results in local point, but it has difficulties in boundary condition and taking long computing time as the number of grid increases. So, there is a need to use alternative method for tunnel fire simulation. A zone model is different kind of CFD method and solves ordinary differential equation based on conservation and auxiliary equations. It shows good macroscopic view in less computing time compared to field model. In this study, therefore, to confirm the applicability of CFAST in tunnel fire analysis, numerical simulations using CFAST are conducted to analyze smoke movement in longitudinal ventilation reduced-scale tunnel fires. Then the results are compared with experimental results. The differences of temperature and critical velocity between numerical results and experimental data are over 30℃ and 0.9m/s, respectively. These values are out of error range. It shows that CFAST 6.0 is hard to be used for tunnel fire simulation.

제목
존 모델을 이용한 종류식 배연 터널 화재시 연기 거동에 대한 수치해석적 연구
제목 (타언어)
A Numerical Study on Smoke Movement in Longitudinal Ventilation Tunnel Fires Using a Zone Model
저자
김현정; 노재성; 유홍선; 김동현; 장용준
발행일
2007-05-17
학회명
2007 한국철도학회 춘계학술대회