능동형 전압제어를 통한 교류 전기철도 급전망에 대한 전력손실 분석

A Power Losses Analysis of AC Railway Power Feeding Network using Adaptive Voltage Control
Citations

SCOPUS

3

초록

This paper compares power losses between voltage controlled before and after using power conversion device in AC feeding system. For this purpose we present voltage control procedures and criteria and model high speed line and train using PSCAD/EMTDC to compare power losses in various feeding condition. Power losses of the simulation result in power control before and after in single point feeding system was reduced maximum 0.37 MW(23.8 %) and average 0.23 MW(20.5 %) when one vehicle load operates maximum load condition. When three vehicles operate maximum load condition in one feeder section, power losses after voltage control was reduced 1.03 MW(49.5%) compared to before voltage control. And, power loss of parallel feeding system is reduced the average 0.08 MW(7.2 %) compared to the single feeding system. In conclusion, adaptive voltage control method using power conversion device can reduce power losses compared with existing method.

키워드

Power losses; Parallel feeding system; Single feeding system; AC railway feeding network; Adaptive voltage control
제목
능동형 전압제어를 통한 교류 전기철도 급전망에 대한 전력손실 분석
제목 (타언어)
A Power Losses Analysis of AC Railway Power Feeding Network using Adaptive Voltage Control
저자
정호성; 김형철; 신승권; 김진호; 윤기용; 조용현
DOI
10.5370/KIEE.2013.62.11.1621
발행일
2013-11
저널명
전기학회논문지
권
62
호
11
페이지
1621 ~ 1627