A study on the characterization of deposited dust on HVAC ducts in subway stations
- 정준식;
- 박덕신;
- 권순박;
- 최성호;
- 김성미;
- 외 2명
초록
This study used various methods to evaluate duct cleanliness and identify the levels of deposited dust in the HVAC systems of subway stations, as well as identifying the characteristics of the pollution sources at the stations. Levels of deposited dust were determined in two subway stations in Seoul from September 2011 to January 2012. The levels of dust deposited on ducts of the stations were measured by visual inspection, the quantitative vacuum test (VT), and the deposit thickness test (DTT). The VT results confirmed that no subway station exceeded a dust deposit of 1.0 g/㎡, which is the recommended surface contamination limit when using the VT method. However, in some supply ducts, the thickness of the dust layer exceeded 60.0㎛, the recommended surface contamination limit when using the DTT method. The visual inspection indicated that platform pollution in subway station A was higher than in the HVAC and waiting rooms, but the difference was insignificant (p
- 제목
- A study on the characterization of deposited dust on HVAC ducts in subway stations
- 저자
- 정준식; 박덕신; 권순박; 최성호; 김성미; 이우석; 전형진
- 발행일
- 2014-11
- 저널명
- International Journal of Environmental Monitoring and Analysis