실내환기 방식이 재채기 토출입자의 거동특성에 미치는 영향

Effect of Ventilation Type on the Trajectory of Coughed Particles in a Hospital Ward

초록

One of purposes in this study was to confirm the behavior of coughed particles under different ventilation conditions. Three types of ventilation systems were applied for this experiment and the properties of coughed particles were measured using computational fluid dynamics (CFD) in an intensive care unit. The changes of total airborne particles for each case showed different trends according to the ventilation type and time, but the deposited particles were similar in all conditions. Although the time taken for 50% of the particles to be deposited was the fastest in case 2, the portion of deposited particles after 300 seconds was only 5% in all conditions. In case 1, a relatively small number of particles were deposited on the wall, but the particle exhaust and deposition on the occupants were the highest. In case 3, the downward ventilation was applied as that recommended by the US Center for Disease Control and Prevention (CDC) and showed different exhaust efficiencies according to the particle size.

키워드

Computational fluid dynamics (CFD); Intensive care unit; Ventilation; Particle deposition; Coughed particles
제목
실내환기 방식이 재채기 토출입자의 거동특성에 미치는 영향
제목 (타언어)
Effect of Ventilation Type on the Trajectory of Coughed Particles in a Hospital Ward
저자
권순박; 송지한; 조영민; 정우태; 박덕신
DOI
10.11629/jpaar.2013.9.2.059
발행일
2013-06
저널명
PARTICLE AND AEROSOL RESEARCH
권
9
호
2
페이지
59 ~ 67